




Available Online
Usually 1-2 weeks before shipment
Not In-Store
In case of additional delays, you will be contacted by one of our sales representative.
Any questions? We are here to help.
The XR315 Surge Eliminator/Power Conditioner from SURGEX is a 120V/15A AC power unit incorporating SurgeX Advanced Series Mode power conditioning and surge protection. The 1RU steel enclosure is designed to be installed in a 19" equipment rack, or placed on a flat surface. A total of eight 120V receptacles are provided on the rear panel. The XR315 incorporates SurgeX ICE Inrush Current Elimination circuitry. The front panel houses a two-line back-lit LCD display which provides status information in normal use and allows interaction with menu items during programming. The character display intensity is adjusted by either a rotary dimmer knob or a push-button On/Off switch. The front panel features two screwdriver-accessible rotary encoders which are used to step through and select from a menu of items to determine the operation of the unit. The power button, when pressed, causes the unit to power up or power down. This button can be disabled if not required. The LED incorporated into the button indicates the status of the unit. When the LED is off the unit is fully powered down; when it is on the unit is fully powered up; when it is flashing the unit is in the process of powering up or down.
A built-in AC voltmeter indicates the line voltage on the LCD display. The internal voltmeter is a peak reading type which was chosen because most electronic equipment incorporates a power supply that charges mostly during the AC peaks. Monitoring the peak of the AC provides a more useful indication of the real voltage available to the electronic equipment plugged into the XR315. A built-in AC ammeter indicates the total current consumption of connected equipment on the LCD display. The internal ammeter is also a peak reading type. A calculation of the total power being delivered to connected equipment is displayed on the second line of the LCD display. Power is calculated as the product of the line voltage and total current draw, and is displayed with the unit Watts "W".
The XR315 is microprocessor controlled and designed to be versatile and expandable. Two or more XR315 units can be connected together to provide control and power conditioning for larger systems. The XR315 can also control other SurgeX products with its auxiliary relay contacts and/or its 12VDC output. All options are set via the front panel and all connections are made at the rear panel. All set-up information is stored in non-volatile memory.
A plug-in Phoenix terminal block on the rear panel accommodates the remote control connections and also the low-voltage outputs. There are three inputs which control power state; one programmable 12VDC output; and one programmable auxiliary relay providing normally open contacts. The inputs can be controlled by an applied DC voltage from 5V to 30V, by a contact closure, or by different types of switch; the input selection being made during programming. The inputs and 12VDC output are designed to withstand incorrect connections including polarity reversal and shorts.
Features
- Eliminates surge energy up to 6,000 V
- Advanced Series Mode
- EMI/RFI filtering
- Catastrophic Over/Under Voltage Shutdown
- ICE Inrush Current Elimination technologies
- All functions easily programmed from the front panel
- Accepts both DC voltage and contact closure control inputs
- Two or more units can be ganged or cascaded together for larger systems
- Programmable auxiliary relay output can be used to control other SurgeX products
- Programmable 12 VDC output can be used to control other SurgeX products
- Auxiliary relay or 12 VDC output can be programmed to provide confirmation feedback products or drive LEDs
- Built-in AC Voltmeter
- Built-in AC Ammeter
- Built-in Power Calculation
- Separate over-ride input can be used to force unit off or force unit on
Specifications
Operational Voltage Range |
90 - 150 VAC
|
Load Rating |
15 A @ 120 VAC
|
Power Rating |
1800 W
|
Power Requirements |
15 W, no load
|
Connectors |
1 x NEMA 5-15P input
8 x NEMA 5-15R output |
Let Through Voltage Rating |
0 V @ 6000 VAC surge
|
UL 1449 TVSS Rating |
1000 surges, 6000 VAC, 3000 A, B3 pulse
|
Suppressed Voltage Rating |
170 VAC
|
Federal Guidelines |
Grade A, Class 1, Mode 1 (CID A-A-55818)
|
EMI/RFI |
Normal Mode (50 Ω load): 40 dB @ 100 kHz, 50 dB @ 300 kHz
50 dB @ 3 MHz, 50 dB @ 30 MHz Common Mode (50 Ω load): 18 dB @ 300 kHz, 30 dB @ 1 MHz 50 dB @ 5 MHz, 50 dB @ 20 MHz |
Maximum Applied Surge Voltage |
6000 VAC
|
Maximum Applied Surge Current |
Unlimited, due to current limiting
|
Maximum Applied Surge Energy |
Unlimited, due to current limiting
|
Endurance |
C62.41-1991 Category B3 pulses:
1 kV >500,000 3 kV >10,000 6 kV >1000 |
Undervoltage Correction |
90 VAC, resume at 100 VAC
|
Overvoltage Correction |
145 VSC, resume at 135 VAC
|
Peak Inrush Current |
1400 Joules during power-up
|
Voltage Range |
Remote Turn-on Applied Voltage Range: 5 - 30 VDC
|
Current Draw |
Contact Closure: 1.5 mA, 100 ohms resistance
5 VDC: 0.1 mA 12 VDC: 1.5 mA 24 VDC: 5.0 mA Remote Control: 4 mA |
Accuracy |
AC Voltmeter Accuracy: ± 2%
AC Ammeter Accuracy: 0.1 A resolution, ±1 A accuracy |
Coaxial |
Compatible with Cable Television (CATV), Digital Satellite System (DSS), Television, Video Cassette Recorder (VCR), Cable Modem, and TV Antenna Equipment. Approvals: UL 497B, UL Recognized
|
Auxiliary Contact Rating |
30 V @ 1 A
|
LED Output |
12 VDC, max 20 mA (resistor required)
|
Temperature Range |
41 to 95°F (5 to 35°C)
|
Humidity Range |
5 to 95% RH, non-condensing
|
Agency Listing |
ETL and cETL certified to (UL 1449; CSA C22.2 No.8-M1986, R2004)
|
Dimensions |
With Rack Ears/Feet: 1.75 x 19.0 x 10.5" (4.5 x 48.3 x 26.7 cm) Without Rack Ears/Feet: 1.7 x 17.3 x 10.5" (4.3 x 43.9 x 26.7 cm)
|
Weight |
12 lb (5.4 kg)
|
Available Online
Usually 1-2 weeks before shipment
Not In-Store
In case of additional delays, you will be contacted by one of our sales representative.
Any questions? We are here to help.